Cleaners and drain openersDescalers

Incruscal F

Safety descaler for closed circuits. Medium strength

Buffered descaling cleaner for water circuits.

Incruscal F

The product

Is an acidic descaling cleaner designed to remove limescale, sludge and rust from all types of closed or open circuits through which water-based coolants or water circulate and which, due to their characteristics, cannot use descalers formulated with strong or oxidising acids.

Is formulated with a high concentration of non-oxidising buffered acids, surfactants, wetting additives and solvents. Thanks to the synergistic action of all its components, calcareous deposits are easily broken down and converted into CO2 and water-soluble salts, improving the heat transfer of the system and additionally reducing the risk of failure due to overpressure. Likewise, sludge and rust are completely solubilised, so that the pipework recovers its original morphology and, with it, the efficiency of the fluid impellers or pumps is restored.

Furthermore, since Incruscal F is based on non-oxidising acids, at the use doses it does not attack the materials commonly used in circuits, such as copper, steel, gaskets, polyethylene, polypropylene or plastic materials in general.

Is also suitable for cleaning drip irrigation systems, as it does not introduce chlorides into the crop. In fact, its use improves phosphorus uptake by the crop.

Is a concentrated product, so its concentration can be adjusted according to the type and quantity of deposits and sludge present, which optimises consumption and reduces cleaning costs.

  • No oxidising acids.
  • Suitable for all types of circuits.
  • High concentration.
  • Removes limescale, sludge and rust.

Incruscal F

Applications

Incruscal F should be used in any situation where it is necessary to remove calcareous deposits, rust and sludge and where extremely aggressive products based on oxidising acids cannot be used.

Incruscal F

Application method

Incruscal F is a concentrated product and must therefore be used diluted in the system.

Cleaning of closed water systems:

1st. Calculate the volume of the equipment or installation to be cleaned.

2nd. Calculate the amount of descaler that will be needed. As a guide, if the deposit thickness is 3–5 mm, the recommended ratio Incruscal F: Water would be 1:3 (1 litre of Incruscal F per 3 litres of water).

3rd. Remove from the circuit the water that will be replaced by Incruscal F and add it. (To improve cleaning efficiency it is recommended not to add the entire quantity in a single dose but to add it in parts progressively. For example: Add ¼ of the calculated product quantity and allow 30–60 minutes to elapse. Then add another ¼ of descaler and allow another 30–60 minutes to elapse. Next, add another ¼ of descaler and allow another 30–60 minutes to elapse. Finally, add the last ¼ of descaler and allow at least another 30–60 minutes to elapse).

4th. Once all the product has been added, allow it to act by recirculation until the circuit is observed to be completely clean. (As a check, a pH measurement of the cleaning solution can be taken. If after completing the cleaning cycle the pH of the solution is below 3, this indicates that residual Incruscal remains in the system and therefore the deposits have been removed. If, on the contrary, the pH is 7 or above, more Incruscal F should be added and a new cleaning cycle carried out).

5th. Finally, remove the cleaning solution from the system and rinse with clean water to remove all residues. (The pH of the system water must not be below 7; if it is, carry out a new rinsing cycle).

IMPORTANT: During the process of dissolving the deposits, CO2 is formed, so it is essential to keep the vent valves or air vents open throughout the entire process to prevent overpressure from building up in the system.

Cleaning of open water systems:

Domestic sanitary water circuits:

Prepare a dilution of 1 part Incruscal F and 4 parts water.

Then dose into the system using an injection pump.

Finally, rinse the system with drinking water.

Irrigation circuits:

Add 25 litres of Incruscal F per hectare of crop to the system, preferably introducing it at the start of the installation.

Finally, rinse the system with water, uncapping the end nozzles of the pipes.

Incruscal F

Technical data

APPEARANCEDENSITYpHCOMPOSITION
Clear colourless liquid1.20 ± 0.01 Kg/L0.5 ± 0.5Buffered inorganic acids, wetting surfactants and solvents